150 kVA diesel generator
150 kVA generators

150 kVA diesel generator — models, fuel consumption and price.

A 150 kVA standby generator delivers about 120 kW at 0.8 power factor (roughly 136 kVA prime). At 75 % load it burns around 18.9 litres of diesel per hour. BRO Global supplies brand-new 150 kVA sets in Saudi Arabia at 60 Hz — open, silent canopy or containerized — with OEM datasheets, manufacturer warranty and a priced offer within 24 hours.

120 kW

Output at 0.8 PF

136 kVA

Prime rating (≈)

18.9 L/h

Fuel at 75 % load (≈)

150 L

8-hour base tank (≈)

What a 150 kVA generator typically powers

  • ✓A commercial building or showroom
  • ✓A mid-size construction site with a tower crane
  • ✓A school, clinic or small factory
  • ✓A restaurant, supermarket or petrol station

Selection chart

Models around 150 kVA we supply

Ratings within about 15 % of 150 kVA at 60 Hz (Saudi grid) and 50 Hz (GCC). Prime shown as standby ÷ 1.1; final figures in the datasheet with your offer.

BRO modelBrandHzStandbyPrimeEngine
PK150-50Perkins50150 kVA136 kVA1106A-70TG1
CU150-50Cummins50150 kVA136 kVA6BTAA5.9-G12
PK165-50Perkins50165 kVA150 kVA1106A-70TAG2
JD165-50John Deere50165 kVA150 kVA6068HF120
BD170-50Baudouin50170 kVA155 kVA6M11G150/5
CU150-60Cummins60150 kVA136 kVA6BTA5.9-G6
PK169-60Perkins60169 kVA154 kVA1106A-70TAG1

Ratings are typical standby kVA at 0.8 PF (1500 rpm at 50 Hz, 1800 rpm at 60 Hz); prime is shown as standby ÷ 1.1. Exact prime/standby ratings, fuel consumption, dimensions and weight are confirmed in the OEM datasheet issued with your offer. Alternator (Leroy Somer / Stamford) and enclosure are selected on the quote form.

Generator FAQ

150 kVA — Generator FAQ

How many kW is a 150 kVA generator?
At the standard 0.8 power factor, 150 kVA equals about 120 kW of usable output. Lighting and IT loads with a higher power factor draw closer to the full kVA; motor-heavy loads draw less.
How much fuel does a 150 kVA generator use?
Roughly 18.9 litres per hour at 75 % load, and about 28.8 litres per hour at full load, depending on the engine. A base tank of about 150 litres gives eight hours of running at 75 % load; larger day tanks and bulk tanks are available.
Should I buy 150 kVA standby or prime?
If the set backs up utility power for limited hours a year, size on the standby rating. If it is your main power source — a camp, a remote site, daily use — size on the prime rating, which is about 10 % lower, so the set runs in its 70–90 % sweet spot.
What is the price of a 150 kVA generator in Saudi Arabia?
Price depends on the engine brand, enclosure (open, silent, containerized), alternator, controller and options such as ATS and fuel tanks. Send us the specification or choose a model above and we reply with a priced offer in SAR, including VAT and delivery, within 24 hours.

Request a quote

Tell us the load. We'll send a priced offer within 24 hours.

The more you share, the sharper the offer — but a kVA and a city are enough to start.